Understanding Hydrant Flow Testing

Understanding Hydrant Flow Testing

Purpose

  1. To provide an overview on the calculations used for hydrant flow testing.


Formula

  1. First Due uses the Hazen-Williams formula to calculate the results of a hydrant flow test.

    The Hazen–Williams equation is an empirical relationship which relates the flow of water in a pipe with the physical properties of the pipe and the pressure drop caused by friction.
    It is used in the design of 
    water pipe systems such as fire sprinkler systemswater supply networks, and irrigation systems. (Source: Wikipedia)


Calculations 

  1. When flow testing hydrants you will need the following information:

    1. Outlet Size
      1. Outlet size is the diameter of the hydrant opening (in inches) that will be used during testing.
    2. Static Pressure
      1. Static Pressure is the pressure that exists at a given point under normal distribution system conditions measured at the residual hydrant with no hydrants flowing. (Source: NFPA 291 3.3.4, 2022 ed.)
    3. Residual Pressure
      1. Residual Pressure is pressure that exists in the distribution system measured at the residual hydrant at the time the flow readings are being measured at flow hydrant(s). (Source: NFPA 291 3.3.3, 2022 ed.)
    4. Coefficient
      1. For hydrant testing there are three coefficients of discharge used: 0.7, 0.8, 0.9.  
        1. The design of the hydrant will determine which of the three coefficients will be used. (Source: NFPA 291 4.9.1, 2022 ed.)



      2. If a stream straightener is used during testing NFPA suggests using 0.95 as the coefficient unless the coefficient of the tube is known. (Source: NFPA 291 4.9.2, 2022 ed.)


  2. Once you have entered the static pressure, residual pressure and coefficient the program will use the Hazen Williams formula to calculate the Rated Capacity of the hydrant.

    1. Rated Capacity is the flow available from a hydrant at the designated residual pressure (rated pressure), either measured or calculated. (Source: NFPA 291 3.3.2, 2002 ed.)

    • Related Articles

    • Documenting Hydrant Flow Testing

      Purpose To explain how to document Hydrant Flow Testing. We recommend reviewing NFPA 291 - Recommended Practice for Fire Flow Testing and Marking of Hydrants to familiarize yourself with flow testing guidelines. Video Directions Navigate to Hydrants ...
    • Methods on starting a Service or Flow Test of a Hydrant

      Purpose To demonstrate the different locations to start a Service or Flow Test of a Hydrant within First Due. Video Directions 1. From the Hydrants List: Using the advance search to filter the list or from saved views, from the actions columns select ...
    • Hydrant Permissions

      Purpose To provide guidance on setting/modifying role permissions for the Hydrants module: Use the "Search Permission" field to quickly find a module’s permission(s) Permissions for the Hydrants Module Hydrant Setup Users can access the Hydrants ...
    • Hydrant Setup

      Purpose To explain the features when setting up the Hydrant Module. Video Information 1. Navigate to Hydrants module then select on Hydrant Setup. 2. There are four areas to manage your Hydrant setup. Notifications - This is an upcoming feature that ...
    • Calculate Needed Fire Flow

      Purpose The purpose of this Knowledge Base Article is to demonstrate the process for calculating the Needed Fire Flow for an Occupancy. Video Instructions 1. Navigate to Admin then click on Roles. 2. Select edit for the Role to enable "Calculate ...